Temperature Controller
1. The inner metal rod will expand on temperature increase on contract as temperature decreases. The change in length is Proportional to the temperature change occurring.
2. The change in length outer metal tube, which has low expansion co-efficient, is negligible. However since one end is attached
To the outer metal tube, the inner rod moves as the outer tube changes length.
3 . The opposite end of the inner rod pushes against and supports a floating link, holding it concentric with a spring loaded Inner valve. With a decrease temperature the inner rod applies pressure on floating link. Causing it to pivot around the Adjustment fulcrum point which tilts the inner valve plug of its seat allowing the output signal to increase. The temperature Adjustment knob adjusts the set point by moving fulcrum point up or down.
| Service | oil/water |
| Operating pressure | 20kg/cm² |
| Temperature | -50⁰F to +750⁰F |
| Set point | provided |
| Insertion length | 295mm |
| Supply | 1.4kg/cm² (natural gas/compressed gas) |
| Output | 0.2 to 1kg/cm² |
| Thermowell | 3/4” NPT threads/SS316 |
| Air Connection | ¼” NPT |
| Action | REVERSE (increase in temp. decreases output) |